Software Manual 146
Automation Tab
Click the Add button to define an Exclusion range.
Starting Reg/Index (Required): Enter the Starting Register for exception class assignments. The valid ranges are 0 to
your configured highest register, and must be less than or equal to Ending Register.
Ending Register (Required): Enter the Ending Register for exception class assignments. The valid ranges are 0 to your
configured highest register, and must be greater than or equal to Starting Register.
Object 2 - Binary Change Event: This field is activated on both Levels 2 and 2+. Its used to determine if a DNP point
will generate events. In case a DNP point generates events (Object2 Binary Change Events) then it should be associ-
ated to a class (Class 1, Class 2 or Class 3), otherwise it should be associated to None. By default all DNP Points don’t
generate events, this feature should be modified by the user.
Click Finish to enter your exclusion into the table.
To edit an entry, select the station in the table and click on the edit button. To delete an existing entry, select the
station in the table and click on the Delete button.
Click on Store I/O Mapping to save your configuration before moving to the next project. Click on the Object Map-
ping button to return to the DNP3 Object Mapping Configuration dialog window.
Binary Outputs Map I/O:
Configure DNP Points: If option is No, then no Binary Outputs are mapped as DNP points.
Highest Register Address (Required): This field is used to show or set the highest register address to map DNP points.
If Configure DNP Points option is set to Yes, the Highest Register Address field is shown to enter a Highest Register
Address value.
Click on Store I/O Mapping to save your configuration before moving to the next project. Click on the Object Map-
ping button to return to the DNP3 Object Mapping Configuration dialog window.